4.1 PLC Connection 4-7
4.1.3 TOYOPUC (Ethernet PC10 Mode)
Communication Setting
Editor
Make the following settings on the editor. For more information, see “1.3.2 Ethernet Communication”.
IP address for the V9 unit
- When specified on the screen program:
[System Setting] [Hardware Setting] [Local Port IP Address]
- When specified on the V9 unit:
Local mode [LAN Setting]
Port number for the V9 unit (for communication with PLC)
[System Setting] [Hardware Setting] [PLC Properties] [Communication Setting]
IP address and port number of the PLC
Register on the [PLC Table] in [System Setting] [Hardware Setting] [PLC Properties] [Target Settings].
PLC
Settings are possible either in the software “PCwin” or ladder programs. For settings using ladder programs, refer to the PLC
manual issued by the manufacturer.
Communication Setting Switches L1 and L2
PCwin
Link parameter setting
Ethernet setting
* When multiple V9 units are connected, make the settings for each unit. A maximum of 32 units can be connected at one time.
Other node table setting
SW No. Item Setting
1L3 SN-IF use setting OFF: Not used (T-OFF)
2 L1 communication setting ON: Link parameter (L1 SEL.)
3 L2 baud rate switching
ON: Auto negotiation (L2 Auto)
OFF: 10M bps (10M)
4 L1 baud rate switching
ON: Auto negotiation (L1 Auto)
OFF: 10M bps (10M)
Item Setting
Rack No. Built-in
Slot No. L1 / L2
Link Module Name Ethernet (32 ports)
Item Setting
Local Node IP Address Set the IP address of the PLC.
Setting 1/Setting 2/
Setting 3/Setting 4/
Setting 1: Connection 1 to 8
Setting 2: Connection 9 to 16
Setting 3: Connection 17 to 24
Setting 4: Connection 25 to 32
Connection 1 - 32 *
Protocol: UDP
Local Node Port No.: Port number of the PLC
Other Node Table No.: Table number for which the V9 is registered
Initialization Initialize using the link parameter
Item Setting
Setting 1/Setting 2
Setting 1: Table 1 to 16
Setting 2: Table 17 to 32
Table 1 to 32 Check each box for “Use”.
Other Node IP Address Set the IP address of the V9.
Other Node Port No. Set the port number of the V9.
1234
O
N
L1 Auto
L2 Auto
L1 SEL.
L3 T-ON
10M
10M
DM
T-OFF