17.1 PLC Connection 17-3
17.1.1 NX7/NX Plus Series (70P/700P/CCU+)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
Be sure to match the settings to those made under [Communication Setting] of the editor.
System Information
Set a station number for the PLC using the PLC software “WINGPC”. For more information, refer to the PLC manual issued by
the manufacturer.
Item Setting Remarks
Connection Mode
1 : 1
/ 1 : n / Multi-link / Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
Signal Level RS-232C
/ RS-422/485
For RS-485 connection, set the transmission delay
time to 3 msec or longer.
Baud Rate 4800 / 9600
/ 19200 / 38400 / 57600 /115K bps 57600 bps and 115K bps supported by NX7R only
Data Length 8 bits
Stop Bit 1 bit
Parity None
Targe t Port No. 0
to 223, 255
Setting Item Setting Remarks
CPU ID 0 to 223, 255