15-10  15. Panasonic
15.1.3 FP Series (UDP/IP)
Communication Setting
Editor
Make the following settings on the editor. For more information, see “1.3.2 Ethernet Communication”.
 IP address for the V9 unit
- When specified on the screen program:
[System Setting]  [Hardware Setting]  [Local Port IP Address]
- When specified on the V9 unit:
Local mode  [LAN Setting]
 Port number for the V9 unit (for communication with PLC)
[System Setting]  [Hardware Setting]  [PLC Properties]  [Communication Setting]
 Others
[System Setting]  [Hardware Setting]  [PLC Properties]  [Communication Setting]
* For settings other than the above, see “1.4 Hardware Settings”.
Item Contents
Header
Select a format of communication with the PLC.
% (Header) / < (Extension Header)
Monitor Registration
Select [Yes] in the case where a monitor registration command is used for communication with the PLC.
* One V9 unit can be registered as a monitor for one PLC. Do not select [Yes] for multiple V9 units in n : 1 
connection.
Local Port No.
Set the local port number of the V9 unit (1 to 31).
Set the same number as the one set for “Target node MEWTOCOL station number” on the [Connection 
Setting] dialog of the PLC.