EasyManua.ls Logo

Fuji Electric Monitouch V9 Series - Q170 Series (Multi Cpu) (Ethernet)

Fuji Electric Monitouch V9 Series
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.1 PLC Connection 9-49
9.1.28 Q170 Series (Multi CPU) (Ethernet)
Communication Setting
Editor
Make the following settings on the editor. For more information, see “1.3.2 Ethernet Communication”.
IP address for the V9 unit
- When specified on the screen program:
[System Setting] [Hardware Setting] [Local Port IP Address]
- When specified on the V9 unit:
Local mode [LAN Setting]
Port number for the V9 unit (for communication with PLC)
[System Setting] [Hardware Setting] [PLC Properties] [Communication Setting]
IP address and port number of the PLC
Register on the [PLC Table] in [System Setting] [Hardware Setting] [PLC Properties] [Target Settings].
On the MT Developer 2, the port number
is specified in hexadecimal notation.
When specifying the port number on the
editor, convert it into a decimal number.
Valid only for 1 : 1 connection
Select the PLC for connection from those
registered on the PLC table.
Set the IP address, port number and
whether or not to use the KeepAlive
function of the PLC.

Table of Contents

Other manuals for Fuji Electric Monitouch V9 Series