9-50 9. MITSUBISHI ELECTRIC
PLC
When using the PLC for the first time, the operating system must be installed.
Make communication settings using the programming tool “MT-Developer2”. For more information, refer to the PLC manual
issued by the manufacturer.
Built-in Ethernet port setting
Specify the IP address and open method on the built-in Ethernet port setting dialog.
Calendar
Normally the calendar of the sequencer CPU, which is specified in the read or write area, is used.
However, if different numbers are specified in the read area and the write area, the calendar of the CPU specified in the read
area is used.
If any device other than the sequencer CPU is specified in the read area and write area, the calendar of the smallest-numbered
sequencer CPU is used.
Item Setting Remarks
IP address (DEC) Specify according to the environment. For more information, refer to the manual of the PLC.
Communication data code Binary code
Enable writing during running Checked
Data can be written from V9 to PLC only when this box is
checked.
If writing of data is attempted while the box is unchecked,
the error “Error code received Receive code 7167” will
occur.
Protocol UDP/TCP Set the same protocol as the one set on the editor.
Open type MC protocol
Local port No. (HEX) Specify according to the environment.
1388H to 1391H cannot be specified because they are
occupied by the system.
When making a setting on the editor, convert the number
specified here into a decimal number.