11-2 11. MOELLER
11.1.1 PS4
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
PRG port
The communication parameters are fixed; baud rate: 9600 bps, signal level: RS-232C, data length: 8 bits, stop bit: 1 bit, parity:
none.
For establishing communication with the V series, register a device memory in the PLC software “S40”. For more information,
refer to the PLC manual issued by the manufacturer.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
*1 The assigned device memory is expressed as shown below when editing the screen.
The addresses are expressed in “bytes”. For word designation, specify an even-numbered address.
Indirect Device Memory Designation
*1 Word designation
Specify an address number divided by “2”.
Example: In the case of MW10, specify “5” (10 divided by 2) for the address number.
*2 Bit designation
Example: In the case of bits 0 to 7 of MW10, specify “5” for the address number and “0” to “7” for the bit designation.
Example: In the case of bits 0 to 7 of MW11, specify “5” for the address number and “8” to “15” for the bit designation.
Item Setting Remarks
Connection Mode 1 : 1
/ Multi-link2 / Multi-link2 (Ethernet)
Signal Level RS-232C
Baud Rate 9600 bps
Data Length 8
bits
Stop Bit 1
bit
Parity None
Device Memory TYPE Remarks
MW (Merker) 00H
M as bit device
*1
Example: MW200
Address number
(even number only)
Example: M200 . 0
Bit number: 0 to 7
Period
Byte address number
Word device Bit device
n+0 Model Device type
n+1
Address No.
*1
n+2 Expansion code
Bit designation
*2
n+3 00 Station number