8.1  PLC Connection 8-13
8.1.10 XGT / XGI Series CNET
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
Set parameters in XG-PD. For more information, refer to the PLC manual issued by the manufacturer.
Communication settings
(Underlined setting: default)
Calendar
This model is equipped with a calendar function; however, the calendar data cannot be written from the V series. Thus, time 
correction must be performed on the PLC side.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for 
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
*1 The assigned device memory is expressed as shown on the 
right when editing the screen.
Item Setting Remarks
Connection Mode
1:1
 / 1:n / Multi-link2 / 
Multi-link2 (Ethernet) / 
1:n Multi-link2 (Ethernet)
Signal Level RS-232C
 / RS-422/485
Baud Rate
4800 / 9600
 / 19200 / 38400 /57600 / 
115200 bps
Data Length   7 / 8
 bits
Stop Bit   1
 / 2 bits
Parity None
 / Odd / Even
Targe t  Port No. 0
 to 31
Item Setting Remarks
Type RS-232C
 / RS-422
Speed
4800 / 9600
 / 19200 / 38400 /57600 / 
115200 bps
Data bit   7 / 8
 bits
Stop Bit   1
 / 2 bits
Parity bit None
 / Odd / Even
Station Number 0
 to 31
Device Memory TYPE Remarks
M (internal memory) 00H MW as word device
Q(output) 01H
QW as word device 
*1
I(input) 02H
IW as word device 
*1
R (internal memory) 03H RW as word device
W (internal memory) 04H WW as word device
F (system flag) 05H FW as word device; FW0 to FW1919: read only
K (PID flag) 06H KW as word device
L (link flag) 07H LW as word device
N (P2P flag) 08H NW as word device
U(analog data register) 09H
UW aw word device 