5-8  5. KEYENCE
5.1.5 KV-700 (Ethernet TCP/IP)
Communication Setting
Editor
Make the following settings on the editor. For more information, see “1.3.2 Ethernet Communication”.
 IP address for the V9 unit
- When specified on the screen program:
[System Setting]  [Hardware Setting]  [Local Port IP Address]
- When specified on the V9 unit:
Local mode  [LAN Setting]
 Port number for the V9 unit (for communication with PLC)
[System Setting]  [Hardware Setting]  [PLC Properties]  [Communication Setting]
 IP address and port number of the PLC
Register on the [PLC Table] in [System Setting]  [Hardware Setting]  [PLC Properties]  [Target Settings].
PLC
KV-LE20
Unit editor setting
(Underlined setting: default)
* These settings can be checked on the access window of the CPU. For more information, refer to the PLC manual issued by the manufacturer.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for 
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Baud Rate 100/10 Mbps Auto
 / 10 Mbps Set to “10 Mbps” (fixed) if the communication status is unstable.
IP Address 0.0.0.0 to 255.255.255.255
Subnet Mask 0.0.0.0 to 255.255.255.255
Port Number (KVS, DB) 8500
TCP/IP
Device Memory TYPE Remarks
DM (data memory) 00H
R (input/output/internal auxiliary/special relay) 01H
TC (timer/current value) 02H
CC (counter/current value) 03H
TS (timer/set value) 04H
CS (counter/set value) 05H
T (timer/contact) 06H
C (counter/contact) 07H
TM (temporary data memory) 08H
CTH (high-speed counter/current value) 09H
CTC (high-speed counter comparator/set value) 0AH
CT (high-speed counter comparator/contact) 0BH
CR (control relay) 0CH
CM (control memory) 0DH