14-2 14. Oriental Motor
14.1.1 High-efficiency AR Series (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Stepping Motor
ARD-AD/ARD-CD
MEXE02 (application software)
Setting changes will take effect after turning the power off and back on. If changes are made to any settings, turn the power
off and on again.
(Underlined setting: default)
Baud rate setting switch (SW2)
Function setting switches (SW4)
Device number setting switch (ID)
Item Setting Remarks
Connection Mode
1 : 1 / 1 : n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
Signal Level RS-422/485
Baud Rate 9600 / 19200 / 38400 / 57600 / 115K bps
Data Length 8
bits
Stop Bit 1
/ 2 bits
Parity None / Odd / Even
Target Port No. 0 to 31 0: Broadcast
Item Setting Remarks
Communication timeout 0
to 10000 ms
0: No check
* If the V series performs no communication for a set timeout
period (other than “0”), an alarm occurs at the stepping motor.
Parity None / Even
/ Odd
Stop bit 1
/ 2 bits
SW2 Setting Item Setting Remarks
Baud rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: 57600 bps
4: 115200 bps
5 to F disabled
SW4 No. Setting Item Setting Remarks
1 Device number setting
OFF: 1 to 15
ON: 16 to 31
Use this switch together with the
device number setting switch (ID).
2
Protocol setting ON: MODBUS protocol
ID Setting Item Setting Remarks
Device number
Use this switch together
with function setting
switch (SW4) No. 1.
* Do not use device
No. 0.
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
12
ON
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
Device No.
Device Number
Setting Switch (ID)
Function Setting
Switch
(SW4) No. 1
1 to 15 1 to F OFF
16 to 31 0 to F ON