16-6 16. RKC
16.1.4 SR-Mini (Standard Protocol)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
SR-Mini
DIP switch
Unit address setting switch
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the controller model. Be sure to set within the range
available for the controller to be used. Use [TYPE] when assigning indirect device memory for macro programs.
* On the signal name reference list, every channel number is designated as
“00”.
Manually enter the value obtained by the following procedure: subtract “1”
from the channel to access, and set the hexadecimal number of the
obtained value.
The assigned device memory is expressed as shown on the right when
editing the screen.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C / RS-422/485
Baud Rate 9600 / 19200 bps
Data Length 7/ 8
bits
Stop Bit 1
/ 2 bits
Parity None
/ Odd / Even
Target Port No. 0 to 15
Switch Setting Contents Remarks
1OFF
8 bits / 1 bit / without parity
OFF, ON: 7 bits, even parity
ON, OFF: 7 bits, odd parity
2OFF
3ON
Baud rate: 9600 bps
OFF, ON: 4800 bps
ON, ON: 19200 bps
4OFF
Switch Setting Remarks
0
to F (= 0 to 15)
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
Device Memory TYPE Remarks
GRP0 (normal: R) 00H Read only
GRP1 (normal: RW) 01H
GRP2 (initial: R) 02H Read only
GRP3 (initial: RW) 03H
Example: GRP0000001 (measurement value for
CH2 temperature)
Channel number: -1 (HEX)
Address