9.1 PLC Connection 9-45
9.1.26 A-Link + Net10
The V9 series can communicate with an A series on the network (Net10) via the standard type link unit.
When the V9 series is connected to a standard type link unit that is mounted on a CPU connected to a data-link system
and network system, the V9 series can access other CPUs on NET II (/B) and NET/10. In such a case, select “A-Link +
Net10” for the V-SFT PLC type.
Accessing other CPUs on NET II (/B) and NET/10 with the V9 series
- On NET II (/B), only CPUs on the same network as the CPU installed with the standard type link unit for connection
with the V9 series (No.1 in above figure) can be accessed.
(Available station numbers: 0 to 64)
- On NET/10, CPUs on networks other than the network with the CPU installed with the standard type link unit for
connection with the V9 series (No.1 in above figure) can be accessed as well (No.2 in above figure).
(Available station numbers: 1 to 64)
Reading and writing device memory for the CPU installed with the standard type link unit for connection with the V9
series (1-1 in above figure)
Set station number 31 for device memory settings on the V-SFT.
The response time becomes the same level as with connection between the V9 series and PLC (1 : 1).
* Note that the response time is slow when writing and reading CPU device memory with station numbers other
than “31” since transient transmission is used.
* Do not use station number “31” for PLCs on a network.
For details on NET II (/B) data link and NET/10 network systems, refer to instruction manuals issued by Mitsubishi.
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
For details on settings for NET II (/B) data link and NET/10 network systems, refer to instruction manuals issued by Mitsubishi.
Standard type link unit
Other than the station number, settings are the same as for “9.1.1 A Series Link”.
Specify “0” for the station number.
The A-link + Net10 can only be selected by the logical port PLC1.
ACPU
ACPUACPU
Net10
Net10 Net10 Net10
ALink
ACPU Net10
V9
1-1 1-2 2-21-3
2-1
Network No. 1
Network No. 2
Station
No. 1
Station
No. 2
Station
No. 3
Station
No. 1
Station
No. 2
Item Setting Remarks
Connection Mode 1 : n
Signal Level RS-232C
/ RS-422/485
Baud Rate 4800 / 9600 / 19200
bps
Transmission Mode Transmission Mode 1
/ Transmission Mode 4
Transmission Mode 1: Without CR/LF
Transmission Mode 4: With CR/LF
Data Length 7
/ 8 bits
Stop Bit 1
/ 2 bits
Parity None / Odd / Even