7.1 PLC Connection 7-9
7.1.2 SR-T (K Protocol)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC
Universal Communication Port
No particular setting is necessary on the PLC. The PLC always performs communication functions using the following
parameters. Set the following parameters under [Communication Setting] of the editor.
Calendar
This model is not equipped with the calendar function. Use the built-in clock of the V series.
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1 : 1
/ Multi-link2 /
Multi-link2 (Ethernet)
Signal Level RS-422/485
Baud Rate 19200
Data Length 8 bits
Stop Bit 1 bit
Parity Odd
Target Port No. 0 to 31
Item Setting
Baud rate 19200 bps
Parity Odd
Data length 8 bits
Stop bit 1 bit
Data type HEX
Device Memory TYPE Remarks
D(word device) 00H
X (input) 01H Common to X and Y
Y (output) 02H Common to X and Y
M (internal relay) 03H
S(stage) 04H
K (keep relay) 05H
L (link relay) 06H
T(timer/contact) 07H
C (counter/contact) 08H