9.1  PLC Connection 9-43
9.1.25 FX 3U/3UC/3G Series Link (A Protocol)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
PLC (PC Parameter)
PLC system (2)
(Underlined setting: default)
Item Setting Remarks
Connection Mode
1:1
 / 1:n / Multi-link / Multi-link2 / 
Multi-link2 (Ethernet) / 
1:n Multi-link2 (Ethernet)
Signal Level RS-232C
 / RS-422/485
Baud Rate 4800 / 9600 / 19200
 bps
Transmission Mode Transmission Mode 1
 / Transmission Mode 4
Data Length 7
 / 8 bits
Stop Bit 1
 / 2 bits
Parity None / Odd / Even
Targe t  Port No. 0  to 31
Item Setting Remarks
Operate communication setting Checked
 RS-232C
When you set Dedicated protocol, 7bits, Even, 1bit, 
19200bps, sum check and form 1: 
D8120 (D8420) = 6896H
 RS-422
When you set Dedicated protocol, 7bits, Even, 1bit, 
19200bps, smacked and form 1: 
D8120 (D8420) = 6096H
* CH1 : D8120, CH2 : D8420
Protocol Dedicated protocol
Data length 7 bits
 / 8 bits
Parity None / Odd
 / Even
Stop bit 1 bit
 / 2 bits
Transmission speed 4800 / 9600
 / 19200 bps
H/W type RS-232C
 / RS-485
Sum check Checked
Transmission control protocol Form 1
 / Form 4
Station number setting 00
 to 0FH