Open setting
Available Device Memory
The available setting range of device memory varies depending on the PLC model. Be sure to set within the range available for
the PLC to be used. Use [TYPE] when assigning indirect device memory for macro programs.
*1 For items where double-words can be used (Num. Display, Graph, Sampling), data is processed as double-words.
For those where bits or words can be used, data is processed as words consisting of lower 16 bits.
For input Upper 16 bits are ignored.
For output ā0ā is written for upper 16 bits.
Item Setting Remarks
Protocol UDP
Fixed buffer Receive, Send
Fixed buffer communication procedure Procedure exist (MC)
Pairing open Enable
Existence confirmation No confirm
Host station Port No. (DEC)
Make settings in accordance with the
network environment.
1025 to 5548, 5552 to 65534
Transmission target device IP address (DEC) IP address of V9
Transmission target device Port No. (DEC) Port No. of V9
Device Memory TYPE Remarks
D (data register) 00H D8000 and later: special register
TN (timer/current value) 01H
CN (counter/current value) 02H
32CN (32-bit counter/current value) 03H *1
M (auxiliary relay) 04H M8000 and later: special relay
S(state) 05H
X (input relay) 06H Read only
Y(output relay) 07H
TS (timer/contact) 08H
CS (counter/contact) 09H
R (extension register) 0BH