7.1 PLC Connection 7-7
SG-8
Universal Communication Port
System parameter setting
Set the station number using the system parameter setting of the programmer. For more information, refer to the PLC manual
issued by the manufacturer.
(Underlined setting: default)
The following settings are fixed; data length: 8 bits, parity: odd, and stop bit: 1 bit.
DIP switch
The DIP switch provided at the rear of the CPU is used to make the following settings.
(Underlined setting: default)
Host Link Module (G-01DM)
Online/offline selector switch
DIP switch (SW1)
(Underlined setting: default)
Item Setting Remarks
Station number 1
to 90 Valid only when DIP switch No. 2 is set to OFF
Data type HEX
Switch Item Setting Remarks
No. 1 Signal level
OFF:
RS-422
ON: RS-232C
No. 2
Station number
setting
OFF:
According to the system parameter setting
ON: Fixed to 01
No. 3
Baud rate
No. 4
Selector Switch Setting
Online
SW1 Item Setting Remarks
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
Station number
setting
1 to 90
For more information on any
station number settings
other than those given on
the left, refer to the PLC
manual issued by the
manufacturer.
No. 8 P-P setting OFF
No. 9
Master/slave
setting
OFF: Slave
1234
ON
OFF
SW3 SW4
9600 bps ON OFF
19200 bps ON ON
ONLINE
OFFLINE
123456
ON
78
9
1 2 3 4 5 6 7
1 ON OFF OFF OFF OFF OFF OFF
2 OFF ON OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF
::::::::
88 OFF OFF OFF ON ON OFF ON
89 ON OFF OFF ON ON OFF ON
90 OFF ON OFF ON ON OFF ON