9-32 9. MITSUBISHI ELECTRIC
PLC
Make the PLC setting using the programming tool “GX-Developer. For more information, refer to the PLC manual issued by
the manufacturer.
L Series Built-in Ethernet
Make the settings for the IP address and the open settings in the Built-in Ethernet port tab window.
Item Setting Remarks
IP address (DEC)
Make settings in accordance with the
network environment.
For more information, refer to the manual of the
PLC.
Communication data code Binary code
Enable online change
(FTP, MC protocol)
Checked
It is not possible to write value from V9 to PLC
when unchecked.
If so, “error code received 7167” occurs.
Protocol UDP/TCP
Set the same protocol as the one set on the
editor.
Open system MC Protocol
Host station port No. (DEC)
Make settings in accordance with the
network environment.
It is not possible to set it from No.5000 to 5009.