EasyManua.ls Logo

Fuji Electric Monitouch V9 Series - Page 247

Fuji Electric Monitouch V9 Series
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-54 9. MITSUBISHI ELECTRIC
Wiring diagram 3 - C4
Hakko Electronics’ cable “D9-MB-CPUQ- M” ( = 2, 3, 5, 10, 15)
When Connected at MJ1/MJ2:
RS-232C
Wiring diagram 1 - M2
According to our noise tests, the attachment of a ferrite core improves noise voltage by 650 to 900 V and aids in preventing communication
errors.
When connecting to the A/QnA series CPU directly, attach a ferrite core to the communication cable to avoid noise problems.
Ferrite cores are optionally available. The model name is “GD-FC” (inner diameter: 8 mm, outer diameter: 20 mm).
In consideration of such noise problems, it is recommended that the standard type link unit be used when the cable length of 15 m or
longer is required.
1
No.
Dsub 9 (Male)
2
3
4
6
7
-RD
-SD
+SD
+RS
5SG
-RS
+RD
FG
CN1
PLC
SDA
DSRA
RDB
SDB
SG
RDA 2
No.
3
4
7
15
16
DSRB
17
20
21
Dsub 25 (Male)
Name Name
5
9
1
6
1
14
13
25
* Use shielded twist-pair cables.
V series
Ferrite core
A/QnA series
CPU
PLC
RD
SD
RS
CS
DR
SG
CD 1
No.
2
3
5
6
7
8
No.
RJ - 45
Dsub 9 (Male)
7
8
5
RD
SD
SG
FG
MJ1/2
NameName
12345678
5
9
1
6
* Use shielded twist-pair cables.

Table of Contents

Other manuals for Fuji Electric Monitouch V9 Series