9.2 Temperature Controller/Servo/Inverter Connection 9-65
9.2.3 MR-J2S-*A
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Servo amplifier
Extension setting parameters
To make the parameter setting valid, the power supply is turned on again.
(Underlined setting: default)
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C
/ RS-422/485
Baud Rate 9600
/ 19200 / 38400 / 57600 bps
Data Length 8 bits (fixed)
Stop Bit 1 bit (fixed)
Parity Even (fixed)
Targe t Port No. 0
to 31
Parameter
No.
Symbol Item Setting Example
15 SNO Station number setting 0
to 31
16 BPS Communication function selection
53 OP8 Function selection 8
0
Response delay time
0: Invalid
1: Valid
Baud rate
0: 9600 bps
1: 19200 bps
2: 38400 bps
3: 57600 bps
Serial communication selection
0: RS-232C
1: RS-422
00 0
Sum check for protocol
0: Provided
Station number selection for protocol
0: With station number