13-14 13. OMRON
CP1 (Built-in RS-232C Port / CP1W-CIFxx)
CPU DIP switch
Set the communication conditions for the CP1H/CP1L optional board slot by using the CPU DIP switch.
PLC system setting
CP1W-CIF11/12 DIP switch
Make the operation setting for the RS-422/485 optional board (CP1W-CIF11/12) by using the DIP switch provided on the
backside.
D32001 D32011 m + 1 m + 11
15 to 04 Reserved -
03 to 00 Baud rate
0: 9600
5: 4800
6: 9600
7: 19200
8: 38400
9: 57600
A: 115200
D32002 D32012 m + 2 m + 12
15 Send delay time
0: 0 ms
1: Random setting
14 to 00 Send delay time random setting
0 to 7530H
Unit: 10 ms
D32003 D32013 m + 3 m + 13
15 CTS control
0: None
1: Provided
14 1 : n/1 : 1 protocol setting
1: 1 : 1 protocol
0: 1 : n protocol
13 to 11 Reserved -
10 to 08 Host link-compatible model mode
07 to 00 Unit No. 00 to 1FH
Switch Contents Setting
SW4 Optional slot 1 communication condition
OFF: According to the setting made on
the PLC system setting
SW5 Optional slot 2 communication condition
OFF: According to the setting made on
the PLC system setting
Item Setting Remarks
User Setting Checked
The system setting can be made by specifying a value for the
address using a programming console.
For more information, refer to the PLC manual issued by the
manufacturer.
Baud Rate 4800 / 9600 / 19200 / 38400 / 57600 / 115200
Parameter 7, 2, E
Mode Host link
Unit No. 00 to 31
Switch Contents Setting
SW1 Terminating resistance ON: Provided
SW2 2-wire / 4-wire selection
ON: 2-wire system
OFF: 4-wire system
SW3 2-wire / 4-wire selection
ON: 2-wire system
OFF: 4-wire system
SW4 Not used OFF
SW5 RS control for RD OFF: Without control
SW6 RS control for SD
ON: With control (when 2-wire system is selected)
OFF: Without control (when 4-wire system is selected)
DM Area
Bit Contents SettingBoard Unit
Port 1 Port 2 Port 1 Port 2