13-20 13. OMRON
13.1.6 SYSMAC CS1/CJ1 (Ethernet Auto)
Communication Setting
Editor
Make the following settings on the editor. For more information, see “1.3.2 Ethernet Communication”.
IP address for the V9 unit
- When specified on the screen program:
[System Setting] [Hardware Setting] [Local Port IP Address]
- When specified on the V9 unit:
Local mode [LAN Setting]
Port number for the V9 unit (for communication with PLC)
[System Setting] [Hardware Setting] [PLC Properties] [Communication Setting]
IP address and port number of the PLC
Register on the [PLC Table] in [System Setting] [Hardware Setting] [PLC Properties] [Target Settings].
Set the same number as the one
specified for [FINS/UDP Port] on
the PLC.
Valid only for 1 : 1 connection
Select the PLC for connection from
those registered on the PLC table.
Set the IP address, port number and
whether or not to use the KeepAlive
function of the PLC.