15-14 15. Panasonic
IP address and port number of the PLC
Register on the [PLC Table] in [System Setting] [Hardware Setting] [PLC Properties] [Target Settings].
Set the same PLC table number as the one set for “No. 410 Unit No.” ([Option] [PLC System Register Setting] [COM1
Port Setting]).
PLC
Make the PLC setting using the communication tool “Configurator WD” and the programming tool “FPWIN GR”. For more
information, refer to the PLC manual issued by the manufacturer.
IP address setting (Configurator WD)
Communication setting (Configurator WD)
COM1 port setting (FPWIN GP)
Valid only for 1 : 1 connection
Select the PLC for connection from those
registered on the PLC table.
Set the IP address, port number and
whether or not to use the KeepAlive
function of the PLC.
Item Setting
Basic Setting
Unit Name Unit name of the communication cassette “AFPX-COM5”
IP Address IP address of the PLC
Subnet mask Subnet mask of the PLC
Gateway Gateway of the PLC
Item Setting
Communication Mode Computer link
Action Mode Server mode
Control unit - Communication cassette Setting Baud rate of COM1 Port 9600 / 115200 bps
Server Setting Source Port No. As desired
Item Setting
No. 410 Unit No.
1 to 99
* The same number must be specified for the PLC table number of the V9.
No. 412 Communication Mode Computer link
No. 413 Communication Format
Data Length 8 bits
Parity Odd
Stop Bit 1 bit
No. 415 Baud rate
9600 / 115200 bps
* Match the baud rate to the one set for “Baud rate of COM1 Port” in the
[Control unit - Communication cassette Setting] of the [Communication
Setting] dialog on the communication tool “Configurator WD”.