16.1 Temperature Controller/Servo/Inverter Connection 16-3
16.1.1 CB100/CB400/CB500/CB700/CB900 (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
CB100
Communication setting mode
When the [R/S] key is pressed while the [SET] key is held down in the PV/SV display mode, the controller enters in the
communication setting” mode.
(Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the controller model. Be sure to set within the range
available for the controller to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-422/485
Baud Rate 4800 / 9600 / 19200 bps
Parity None
/ Odd / Even
Data Length 8 bits
Stop Bit 1 bit
Target Port No. 1 to 31
Indication Item Setting Remarks
Add Slave address 1 to 31 Communication is not performed when “0” is set.
bPS Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
bIT Data configuration
0: 8 bits / 1 bit / none
6: 8 bits / 1 bit / even
7: 8 bits / 1 bit / odd
InT Interval time setting 0 to 150 Interval time = set value 1.666 ms
Device Memory TYPE Remarks
--- 00H