EasyManua.ls Logo

GE Baker Hughes PanaFlow LC XMT1000 - H.9 Analog Input Block; H.10 PID Block

GE Baker Hughes PanaFlow LC XMT1000
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix H. Foundation Fieldbus Communication
146 PanaFlow™ LC User’s Manual
H.4.2 Password
A password must be entered to change XMT1000 system parameters. This can be done using Foundation
Fieldbus. There are different levels of security for different Passwords (
Admin or Operator). Please see the
standard manual for more detail on password levels. Figure 132 below shows the password fields in the
XMT1000 Resource Block.
Figure 132: Password Fields in XMT1000 Resource Block
To Enter configuration mode, complete the following steps:
1. Select the
Resource Block > Others tab.
2. Select
SYSTEM_OPT_TYPE and set to Option FI.
3. Select
SYSTEM_REQ_LEVEL and set to Admin or Operator.
4. Enter the
Admin or Operator password into the SYSTEM_REQ_PASS field.
5. Select
Cancel from the SYSTEM_REQ_CMD drop down box.
6. Select
Login from the SYSTEM_REQ_CMD drop down box.
7. Click on the
Write Changes button.
8. Verify that
S1:In Config Mode appears on XMT1000 display. You should now be able to edit fields with
Admin privileges.
Attention! Before entering a password, make sure the
XMIT_TB transducer block is in active mode.

Table of Contents

Related product manuals