CHAPTER 5: SETTINGS PRODUCT SETUP
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-117
5
5.3.11 User-programmable LEDs
5.3.11.1 Menu - Enhanced and standard front panels
SETTINGS PRODUCT SETUP  USER-PROGRAMMABLE LEDS
5.3.11.2 Menu - Graphical front panel
SETTINGS PRODUCT SETUP  USER-PROGRAMMABLE LEDS
The LEDs can be customized to illuminate when a selected FlexLogic operand is in the logic 1 state. The trip and alarm
LEDs can also be customized in a similar manner. To ensure correct functionality of all LEDs, an LED test feature is also
provided.
5.3.11.3 LED test
SETTINGS PRODUCT SETUP  USER-PROGRAMMABLE LEDS LED TEST
When enabled, the LED test can be initiated from any digital input or user-programmable condition, such as a user-
programmable pushbutton. The control operand is configured under the
LED TEST CONTROL setting. The test covers all
LEDs, including the LEDs of the optional user-programmable pushbuttons.
For the enhanced and standard front panels, the test consists of the following three stages:
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned.” This stage lasts as
long as the control input is on, up to a maximum of one minute. After one minute, the test ends.
2. All the LEDs are turned off, and then one LED at a time turns on for one second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for one second, then back on. The test routine starts at the top
left panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to
more than one LED being turned off from a single logic point. This stage can be interrupted at any time.
USER-PROGRAMMABLE
LEDS
LED TEST
See below
TRIP & ALARM LEDS
See page 5-119
USER-PROGRAMMABLE
LED 1
See page 5-119
USER-PROGRAMMABLE
LED 48
USER-PROGRAMMABLE
LEDS
LED TEST
See below
TRIP & ALARM LEDS
See page 5-119
EVENT CAUSE LED 1
See page 5-120
EVENT CAUSE LED 9
LED TEST
LED TEST FUNCTION:
Disabled
Range: Disabled, Enabled
LED TEST CONTROL:
Off
Range: FlexLogic operand