CHAPTER 5: SETTINGS CONTROL ELEMENTS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-251
5
Figure 5-133: Neutral voltage unbalance logic
5.8 Control elements
5.8.1 Overview
Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of
this chapter for information.
5.8.2 Trip bus
SETTINGS  CONTROL ELEMENTS TRIP BUS  TRIP BUS 1(6)
TRIP BUS 1
TRIP BUS 1
FUNCTION: Disabled
Range: Enabled, Disabled
TRIP BUS 1 BLOCK:
Off
Range: FlexLogic operand
TRIP BUS 1 PICKUP
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
TRIP BUS 1 RESET
DELAY: 0.00 s
Range: 0.00 to 600.00 s in steps of 0.01