CHAPTER 5: SETTINGS CONTROL ELEMENTS
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL 5-253
5
TRIP BUS 1 RESET — The trip bus output is reset when the operand assigned to this setting is asserted. Note that the RESET OP
operand is pre-wired to the reset gate of the latch, As such, a reset command from the front panel interface or via
communications resets the trip bus output.
Figure 5-135: Trip bus logic
5.8.3 Setting groups
SETTINGS  CONTROL ELEMENTS SETTING GROUPS
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
GROUPED
ELEMENTS
settings menu. The active setting group can be indicated on the front display of the UR by configuring User-
Programmable LEDs to display the state of the SETTING GROUP ACT FlexLogic operands.
SETTING GROUPS FUNCTION — When Enabled, allows setting groups other than group 1 (the default active group) to be
activated. The default setting group is forced active while the SETTING GROUPS FUNCTION setting is Disabled.
SETTING GROUPS
SETTING GROUPS
FUNCTION: Enabled
Range: Disabled, Enabled
SETTING GROUPS BLK:
Off
Range: FlexLogic operand
GROUP 2 ACTIVATE ON:
Off
Range: FlexLogic operand
GROUP 6 ACTIVATE ON:
Off
Range: FlexLogic operand
GROUP 1 NAME: Range: up to 16 alphanumeric characters
GROUP 6 NAME: Range: up to 16 alphanumeric characters
SETTING GROUP
EVENTS: Disabled
Range: Disabled, Enabled