EasyManuals Logo

GE C70 User Manual

GE C70
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #528 background imageLoading...
Page #528 background image
6-10 C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
STATUS CHAPTER 6: ACTUAL VALUES
6
6.3.17 Direct devices status
ACTUAL VALUES STATUS  DIRECT DEVICES STATUS
These actual values represent the state of direct devices 1 through 16.
6.3.18 Teleprotection channel tests
ACTUAL VALUES STATUS  TELEPROT CH TESTS
The status information for two channels is shown here.
CHANNEL 1 STATUS — This represents the receiver status of each channel. If the value is “OK,” teleprotection is enabled and
data is being received from the remote terminal; If the value is “FAIL,” teleprotection enabled and data is not being received
from the remote terminal. If “n/a,” teleprotection is disabled.
CHANNEL 1 LOST PACKETS — Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle.
The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS  CLEAR RECORDS menu.
VALIDITY OF CHANNEL CONFIGURATION — This value displays the current state of the communications channel identification
check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the “FAIL” message
displays. The “N/A” value appears if the local relay ID is set to a default value of “0,” the channel is failed, or if the
teleprotection inputs/outputs are not enabled.
6.3.19 Remaining connection status
ACTUAL VALUES STATUS  COMM STATUS REMAINING CONNECT
DIRECT DEVICES
STATUS
DIRECT DEVICE 1
STATUS: Offline
Range: Offline, Online
DIRECT DEVICE 16
STATUS: Offline
Range: Offline, Online
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK
CHANNEL 1 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
CHANNEL 2
STATUS: n/a
Range: n/a, FAIL, OK
CHANNEL 2 LOST
PACKETS: 1
Range: 1 to 65535 in steps of 1
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
Range: n/a, FAIL, OK
COMM STATUS
REMAINING CONNECT
MMS TCP(max 5)
5
Range: 0 to 5
MODBUS TCP (max 4)
4
Range: 0 to 4
DNP TCP(max 2)
2
Range: 0 to 2
IEC-104 TCP(max 2)
2
Range: 0 to 2
SFTP (max 4)
4
Range: 0 to 4

Table of Contents