GEK-106237P MIFII Digital Feeder Relay 5-7
5 SETTINGS 5.3 ADVANCED SETTINGS
5
5.3ADVANCED SETTINGS
NOTE ABOUT THE TRIP MIN TIME SETTING:
This setting indicates the time during which the tripping contact will remain closed as a minimum in case of fault. If the fault
persists for a longer time than the set value, the tripping contact will remain closed and will be opened immediately after the
fault is cleared, while if the fault is shorter than the set time, the relay will maintain the contact closed for this set time.