4–272 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING CHAPTER 4: SETPOINTS
DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 50.000 s
The setting provides the definite Switch-In and Switch-Out time delay. Instantaneous
operation is selected by the time delay setting of 0.000 s.
MINIMUM VOLTAGE
Range: 0.00 to 1.25 x VT in steps of 0.01 x VT
Default: 0.30 x VT
The setting sets the minimum voltage for Power Factor element operation specified per
times VT.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see Common Setpoints
.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset