D.1.5 IEC 60870-5-104 POINT LIST
a) SELECTION OF STANDARD ASDUS:
Process information in monitor direction
<1> Single-point information M_SP_NA_1
<2> Double-point information M_DP_NA_1
<3> Measured value, short floating point value M_ME_NC_1
Process information in control direction
<46> Single command C_SC_NA_1
System information in control direction
<106> Reset process command C_RP_NA_1
The F650 relay has a custom Binary Inputs points list, called
User Map; it is common for any protocol. In the
case of IEC 104 Protocol, those points are GROUP1 and GROUP2.
GROUP 1 STATUS
POINT DESCRIPTION
M_ SP_NA_1 Points
1000-1063 CONTROL EVENTS
GROUP 2 STATUS
POINT DESCRIPTION
M_ SP_NA_1 Points
1064-1127 CONTROL EVENTS
GROUP 3 STATUS
POINT DESCRIPTION
M_ DP_NA_1 Points
1500-1515 SWITCHGEAR EVENTS