7-10 W650 Wind Generator Protection System GEK-113032A
7.2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL
7
SERVICES AA: TP/MC SERVER (S) W650
TRANSMISSION OF SAMPLE VALUE MODEL (SVC) (CLAUSE 16)
MULTICAST SVC
S45 SendMSVMessage MC c10
S46 GetMSVCBValues TP O
S47 SetMSVCBValues TP O
UNICAST SVC
S48 SendUSVMessage MC c10
S49 GetUSVCBValues TP O
S50 SetUSVCBValues TP O
c10- shall declare support for at least one (SendMSVMessage or SendUSVMessage)
CONTROL (CLAUSE 17.5.1)
S51 Select TP O
S52 SelectWithValue TP O
S53 Cancel TP O
S54 Operate TP M Yes
S55 Command-Termination TP O
S56 TimeActivated-Operate TP O
FILE TRANSFER (CLAUSE 20)
S57 GetFile TP M Yes
S58 SetFile TP O
S59 DeletFile TP O
S60 GetFileAttributeValues TP M Yes
SERVICES COMMENTS
TIME (CLAUSE 5.5)
T1 Time resolution of internal clock 10 Nearest negative power of 2 in seconds
T2 Time accuracy of internal clock T0
T1
YT2
T3
T4
T5
T3 Supported TimeStamp resolution 10 Nearest value of 2**-n in seconds according
to 5.5.3.7.3.3 of Part 7-2