GEK-113032A W650 Wind Generator Protection System 7-39
7 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR W650
7
c) CONTROLABLE INTEGER STATUS (INC).
7.2.4.4 COMMON DATA CLASS SPECIFICATIONS FOR STATUS SETTINGS
a) SINGLE POINT SETTING (SPG).
INC CLASS (CONTROLLABLE INTEGER STATUS)
GEMODINC
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DATAATTRIBUTE
status
StVal INT32 ST dcgh M
q BVstring13 ST qchg M
t Utctime ST M
configuration, descripcion and extension
ctlModel ENUMERATED CF M
d Vstring255 DC O
GEINC
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DATAATTRIBUTE
control and status
Oper
ctlVal Boolean CO AC_CO_M
origin Originator CO,ST AC_CO_M
orCat ENUMERATED M
orIdent OCTECT64 M
ctlNum INT8U CO,ST M
tBtime6 CO M
Test Boolean CO M
Check ENUMERATED CO M
StVal INT32 ST dcgh M
q BVstring13 ST qchg M
t Utctime ST M
configuration, descripcion and extension
ctlModel ENUMERATED CF M
d Vstring255 DC O
SPG CLASS (SINGLE POINT SETTING)
GESPG
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DATAATTRIBUTE
setting
setVal Boolean SP AC_NSG_M
configuration, descripcion and extension
d Vstring255 DC O