7-38 W650 Wind Generator Protection System GEK-113032A
7.2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL
7
b) CONTROLABLE DOUBLE POINT (DPC).
DPC CLASS (CONTROLLABLE DOUBLE POINT)
GEDPC (PARTICULARIZACIÓN OPERATE)
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C
DataAttribute
control and status
Oper
ctlVal Boolean CO AC_CO_M
origin Originator CO,ST AC_CO_M
orCat ENUMERATED M
orIdent OCTECT64 M
ctlNum INT8U CO,ST M
TBtime6 CO M
Test Boolean CO M
Check ENUMERATED CO M
StVal CODE ENUM ST dchg intermediate-state | off | on | bad-state M
q BVstring13 ST qchg AC_ST
t Utctime ST AC_ST
configuration, descripcion and extension
ctlModel ENUMERATED CF M
d Vstring255 DC O