B-100 W650 Wind Generator Protection System GEK-113032A
B.7 MEMORY MAP APPENDIX B
B
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS
Ajustes Unidad Direccional de Tierra Sensible Grupo 1 - Sensitive Ground Directional 1
0x2E59 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E5A MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E5C Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
0x2E5D Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E5E Pol V Threshold F003 1 R/W 2 [0 , 500] V
0x2E60 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E73 Confirmation address W 1
Ajustes Unidad Direccional de Tierra Sensible Grupo 2 - Sensitive Ground Directional 2
0x2E74 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E75 MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E77 Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
0x2E78 Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E79 Pol V Threshold F003 1 R/W 2 [0 , 500] V
0x2E7B Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E8E Confirmation address W 1
Ajustes Unidad Direccional de Tierra Sensible Grupo 3 - Sensitive Ground Directional 3
0x2E8F Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2E90 MTA F003 1 R/W 2 [-90 , 90] Deg
0x2E92 Direction F012 1 R/W 1 0=REVERSE
1=FORWARD
0x2E93 Block Logic F012 1 R/W 1 0=PERMISSION
1=BLOCK
0x2E94 Pol V Threshold F003 1 R/W 2 [0 , 500] V
0x2E96 Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2EA9 Confirmation address W 1
Ajustes Demanda - Demand
0x2F07 Demand Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2F08 CRNT Demand Method F012 1 R/W 1 0=THERMAL EXPONENTIAL
1=BLOCK INTERVAL
2=ROLLING DEMAND
0x2F09 POWER Demand Method F012 1 R/W 1 0=THERMAL EXPONENTIAL
1=BLOCK INTERVAL
2=ROLLING DEMAND
0x2F0A Demand Interval F012 1 R/W 1 0=5 Minutes
1=10 Minutes
2=15 Minutes
3=20 Minutes
4=30 Minutes
5=60 Minutes