GEK-113032A W650 Wind Generator Protection System B-101
APPENDIX B B.7 MEMORY MAP
B
ADDRESS BIT NAME FORMAT STEP MODE LENGTH MISCELLANEOUS
Ajustes Demanda - Demand
0x2F0B Trigger Enabled F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2F0C Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2F1F Confirmation address W 1
Ajustes Protocolo IEC 870-5-104
0x2F20 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x2F21 TCP Port F005 1 R/W 2 [0 , 65535]
0x2F23 Common Addr of ASDU F005 1 R/W 2 [0 , 65535]
0x2F25 Cyclic Meter Period F005 1 R/W 2 [0 , 3600]
0x2F27 Synchronization Event F005 1 R/W 2 [0 , 3600]
0x2F5A Confirmation address W 1
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 1 - Phase TOC Low 1
0x32A5 Function F012 1 R/W 1 0=DISABLED
1=ENABLED
0x32A6 Input F012 1 R/W 1 0=PHASOR(DFT)
1=RMS
0x32A7 Pickup Level F003 1 R/W 2 [0.05 , 160.00] A
0x32A9 Curve F012 1 R/W 1 0=IEEE Ext Inv
1=IEEE Very Inv
2=IEEE Mod Inv
3=IEC Curve A
4=IEC Curve B
5=IEC Curve C
6=IEC Long-Time Inv
7=IEC Short-Time Inv
8=IAC Ext Inv
9=IAC Very Inv
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite Time
17=Rectifier Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
0x32AA TD Multiplier F003 1 R/W 2 [0.00 , 900.00] s
0x32AC Reset F012 1 R/W 1 0=INSTANTANEOUS
1=LINEAL
0x32AD Voltage Restraint F012 1 R/W 1 0=DISABLED
1=ENABLED
0x32AE Snapshot Events F012 1 R/W 1 0=DISABLED
1=ENABLED
0x32C1 Confirmation address W 1