E-14 W650 Wind Generator Protection System GEK-113032A
E.1 FACTORY DEFAULT SETTINGS APPENDIX E
E
SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Pickup level Pickup Level 50.50 0.01 Hz [20.00 : 65.00]
Trip time Trip Delay 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Delay 0.00 0.01 s [0.00 : 900.00]
Minimum voltage threshold Minimum Voltage 50 1 V [30 : 500]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Maximum Number of shots Max Number Shots 1 N/A [1 : 4]
Dead time 1 Dead Time 1 0.00 0.01 s [0.00 : 900.00]
Dead time 2 Dead Time 2 0.00 0.01 s [0.00 : 900.00]
Dead time 3 Dead Time 3 0.00 0.01 s [0.00 : 900.00]
Dead time 4 Dead Time 4 0.00 0.01 s [0.00 : 900.00]
Reclaim time or reset lockout delay Reclaim Time 0.00 0.01 s [0.00 : 900.00]
Reclose conditions permission Cond. Permission DISABLED N/A [DISABLED – ENABLED]
Hold time Hold Time 0.00 0.01 s [0.00 : 900.00]
Reset time Reset Time 0.00 0.01 s [0.00 : 900.00]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
USER
VALUE
Function permission Function DISABLED N/A [DISABLED – ENABLED]
Snapshot event generation Snapshot Events ENABLED N/A [DISABLED – ENABLED]