Figure 40: Ipos and Ineg current waveforms
Based on the R
ct ratio and discriminative criteria explained above, the example below shows the relay initially
detecting an external fault before switching to internal fault at the 0.7 seconds.
E00772
Figure 41: Internal external fault binary
P54A/B/C/E Chapter 6 - Current Differential Protection
P54xMED-TM-EN-1 111