4 CIRCUIT BREAKER FAIL LOGIC
4.1 CIRCUIT BREAKER FAIL LOGIC - PART 1
Enabled
Aid1 WI Trip 3Ph
WI Prot Reset
Aid2 WI Trip 3Ph
1
Aid 1 WI Trip A
Aid 2 WI Trip A
1
&
&
Aid 1 WI Trip B
Aid 2 WI Trip B
1
Aid 1 WI Trip C
Aid 2 WI Trip C
1
&
&
&
&
&
&
WIINFEEDA
WIINFEEDB
WIINFEEDC
1
1
1
V00729
ExtTrip Only Ini
Enabled
Note: This part is not relevant for non -distance models
ExtTrip Only Ini
Enabled
CurrentProtSEFTrip
ISEF<FastUndercurrent
&
TripStateSEF
ZCD function
ZCDStateSEF
ZCDStateA
ZCDStateB
ZCDStateC
RD
Q
S
642
652
637
647
638
648
639
649
Figure 93: Circuit Breaker Fail logic - part 1
P54A/B/C/E Chapter 8 - CB Fail Protection
P54xMED-TM-EN-1 187