10 ENVIRONMENTAL CONDITIONS
10.1 AMBIENT TEMPERATURE RANGE
Compliance IEC 60255-27: 2005
Test Method IEC 60068-2-1:2007 and IEC 60068-2-2 2007
Operating temperature range -25°C to +55°C (continuous)
Storage and transit temperature range -25°C to +70°C (continuous)
10.2 TEMPERATURE ENDURANCE TEST
Temperature Endurance Test
Test Method IEC 60068-2-1: 1993 and 60068-2-2: 2007
Operating temperature range
-40°C (96 hours)
+70°C (96 hour
s)
Storage and transit temperature range
-40°C (96 hours)
+70°C (96 hour
s)
10.3 AMBIENT HUMIDITY RANGE
Compliance IEC 60068-2-78: 2001 and IEC 60068-2-30: 2005
Durability 56 days at 93% relative humidity and +40°C
Damp heat cyclic six (12 + 12) hour cycles, 93% RH, +25 to +55°C
10.4 CORROSIVE ENVIRONMENTS
Compliance IEC 60068-2-42: 2003, IEC 60068-2-43: 2003
Industrial corrosive environment/poor environmental
contr
ol, Sulphur Dioxide
21 days exposure to elevated concentrations (25ppm) of SO
2
at
75% r
elative humidity and +25°C
Industrial corrosive environment/poor environmental
contr
ol, Hydrogen Sulphide
21 days exposure to elevated concentrations (10ppm) of H
2
S at
75% r
elative humidity and +25°C
Salt mist IEC 60068-2-52: 1996 KB severity 3