EasyManuals Logo

GE P54C User Manual

GE P54C
850 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #552 background imageLoading...
Page #552 background image
10 ENVIRONMENTAL CONDITIONS
10.1 AMBIENT TEMPERATURE RANGE
Compliance IEC 60255-27: 2005
Test Method IEC 60068-2-1:2007 and IEC 60068-2-2 2007
Operating temperature range -25°C to +55°C (continuous)
Storage and transit temperature range -25°C to +70°C (continuous)
10.2 TEMPERATURE ENDURANCE TEST
Temperature Endurance Test
Test Method IEC 60068-2-1: 1993 and 60068-2-2: 2007
Operating temperature range
-40°C (96 hours)
+70°C (96 hour
s)
Storage and transit temperature range
-40°C (96 hours)
+70°C (96 hour
s)
10.3 AMBIENT HUMIDITY RANGE
Compliance IEC 60068-2-78: 2001 and IEC 60068-2-30: 2005
Durability 56 days at 93% relative humidity and +40°C
Damp heat cyclic six (12 + 12) hour cycles, 93% RH, +25 to +55°C
10.4 CORROSIVE ENVIRONMENTS
Compliance IEC 60068-2-42: 2003, IEC 60068-2-43: 2003
Industrial corrosive environment/poor environmental
contr
ol, Sulphur Dioxide
21 days exposure to elevated concentrations (25ppm) of SO
2
at
75% r
elative humidity and +25°C
Industrial corrosive environment/poor environmental
contr
ol, Hydrogen Sulphide
21 days exposure to elevated concentrations (10ppm) of H
2
S at
75% r
elative humidity and +25°C
Salt mist IEC 60068-2-52: 1996 KB severity 3
Chapter 22 - Technical Specifications P54A/B/C/E
526 P54xMED-TM-EN-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE P54C and is the answer not in the manual?

GE P54C Specifications

General IconGeneral
BrandGE
ModelP54C
CategoryRelays
LanguageEnglish

Related product manuals