CLEANING THE GENERATOR
Caked or greasy dirt may be loosened with a soft brush or
a damp cloth. A Vacuum system may be used to clean up
loosened dirt. Dust and dirt may also be removed using dry,
low-pressure air (25 psi maximum).

Do not use sprayed water to clean the Generator. Some
of the water will remain on the Generator windings and
terminals and may cause very serious problems.
DRYING THE GENERATOR
The procedure for drying an alternator is as follows:
1. Open the Generator main circuit breaker.

Generator should have no electrical loads applied while
drying.
2. Disconnect all wires in a manner that allows the alternator
to be completed disconnected.
3. Provide an external source to blow warm, dry air through
the Generator interior (around the rotor and stator
windings.

Do not exceed 185º F (85ºC).
4. Re-connect stator lead.
5. Start the Generator and let it run for 2 or 3 hours.
6. Shutdown the Generator and repeat the insulation
resistance tests.
Section 1.5
Testing, Cleaning and Drying

Table of Contents

Other manuals for Generac Power Systems 7 kW NG

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems 7 kW NG and is the answer not in the manual?

Generac Power Systems 7 kW NG Specifications

General IconGeneral
BrandGenerac Power Systems
Model7 kW NG
CategoryPortable Generator
LanguageEnglish

Related product manuals