HT# 059299-00 A
• The Multi-MOD Platinum is equipped with two Modulating Output Cards
While the extension can accept up to four output cards Every two modulating
boiler outputs are controlled by one Modulating Output Card See "Multi-MOD
Platinum Back Chart" on page 9 and "Extension Function Chart" on page 10
• The cards are installed on the back of the control's main board
• There are two types of cards available:
◦ 135Ω Cards (HT# 900203-135): operates two 135 Ohm modulating motors
◦ Current/Voltage Cards (HT# 900201-C/V): operates two 4-20mA, 0-10V,
0-5V, 2-10V, or 1-5V modulating motors Each card can provide only one
output signal Afx the Current Voltage label below the Modulation Output
terminals (C1 through C12)
• The Multi-MOD Platinum comes with its Modulating Output cards installed
However, when ordering Extension Modules, the Modulating Output Cards
must be ordered separately
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
STAGEHELP NEXT
PRESS TO
SELECT
BACK
SYS= 125
o
F OD= 31
o
F
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
4-20 mA
SYSTEM
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
TGT= 126
o
F
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
SYSTEM B
A
1 2 3 4
5 6 7 8 9 10
11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
• The Multi-MOD Platinum is equipped with an 80 character (4 lines x 20
character) bright digital display
• All the menus are in English
• The default main display is divided into four rows
○ First Row: displays System and Outdoor sensor values
○ Second Row: displays important messages
○ Third Row: displays stage letters It also displays the lead stage in
brackets
○ Fourth Row: displays stage ring or lockout status
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
STAGEHELP NEXT
PRESS TO
SELECT
BACK
SYS= 125
o
F OD= 31
o
F
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
4-20 mA
SYSTEM
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
TGT= 126
o
F
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
SYSTEM B C DA
LINE
NEUTRAL
SYS
B C DA
1 2 3 4
5 6 7 8 9 10 11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
STAGEHELP NEXT
PRESS TO
SELECT
BACK
SYS= 125
o
F OD= 31
o
F
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
4-20 mA
SYSTEM
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
TGT= 126
o
F
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
SYSTEM B C DA
LINE
NEUTRAL
SYS
B C DA
1 2 3 4
5 6 7 8 9 10 11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
When in the menus, rotate the knob to scroll through the menus
When in a setting, scroll to change the setting
Press the knob to enter the selected menu or to accept the current settings value
In the default screen, pressing it shows the date, time, and space average
Is used to go to the previous menu
In Boiler menu, goes to the next setting
In Schedules, goes to next schedule time on schedules,
From the default screen, pressing it enters the Stage menu
In the Stage menu, switches between stages
In Schedules, switches between different weekdays,
In Schedules, clears a specic schedule setting
In Stage menu, goes to previous boiler settings
When clicked in a specic menu item provides help instructions