• When All-On is selected, the Multi-MOD Platinum will turn all stages
On to a 100% when the System sensor reads Short or Open and the
outdoor temperature is below Outdoor Cutoff If the outdoor temperature
was above the Outdoor Cutoff; the Season was set to Summer; or the
Shutdown was active, the Multi-MOD Platinum will turn all the stages off
• When Shutdown is selected, the Multi-MOD Platinum will turn all stages
Off when the System sensor reads
Short or Open
• When All-On is selected, the Multi-MOD Platinum will maintain the
Minimum Target temperature when the Outdoor reads
Short or Open
• When Shutdown is selected, the Multi-MOD Platinum will maintain the
Maximum Target temperature when the Outdoor reads
Short or Open
/<System Startup>/ Sensor Type/.../Sensor Fault Mode/ Fast Cool Down
• The Fast Cool Down allows the building to cool down quicker when
starting the Night Schedule It does that by lowering the target
temperature until the Space Average drops to the Night Target
• For the Fast Cool Down to function, the Space Lock must be set to ON
See "Space Lockout" on page 45
• When Minimum Water Temp is selected, the Multi-MOD Platinum reduces
the target temperature to the Minimum Target temperature when the
Schedule switches from Day (Normal) to Night (Saving) This option
must be selected when the boiler manufacturer has a minimum boiler
temperature requirement
• When Off is selected, the Multi-MOD Platinum reduces the target water
temperature to a minimum of 70°F when the Schedule switches from Day
(Normal) to Night (Saving)
• When the building space temperature reaches the Night Target setting the
Multi-MOD Platinum will exit the Fast Cool Down operation and start its
night heating level
- FAST COOL DOWN -
Minimum Water Temp
No Heat
/<System Startup>/ Sensor Type/.../ Fast Cool Down/Day Light Saving
• Enable this feature to account for the time changes in areas where Day
Light Saving is observed
DAY LIGHT SAVINGS
Enable
Disable