HT# 059299-00 A
• Vari-Boost begins before 6 am and ends at 6 am
• Day temperature is maintained from 6 am until before 10 PM
• Early Shutdown starts before 10 PM and ends at 10 PM
• Night temperature is maintained from 10 PM until the Vari Boost the
following morning
• Vari Boost begins before 7 am and ends at 7 am
• Day temperature is maintained from 7 am to 11 am
• Night temperature is maintained from 11 am to 1 PM
• Day temperature is maintained from 1 PM to 4 PM
• Night temperature is maintained from 4 PM to 6 PM
• Day temperature is maintained from 6 PM until before 10 PM
• Early Shutdown starts before 10 PM and ends at 10 PM
• Night temperature is maintained from 10 PM until the following morning
• No Vari Boost because the #1 is not programmed
• Day temperature is maintained from 8 am until before 4 PM
• Early Shutdown starts before 4 PM and ends at 4 PM
• Night temperature is maintained from 4 PM into Sunday
• Night temperature is maintained all day Sunday, ending at the Vari Boost
Monday morning
If the control has space sensors configured, Boost can extend to an
additional hour if Day Target was not reached within the Boost period
/<Schedules>/Copy Schedule
• This feature copies all Monday's schedule to the rest of the week
------ SCHEDULES ------
Copy Mon Schedules
To All Other Days
(Select to Execute)
/<Schedules>/Set Date & Time
• To use the schedules, set the Date and Time
• Internet capable controls get their date and time from the Internet
based on the Building Time Zone setting in the ICMS website
---- DATE & TIME ---
Date Mon 10/20/12
Time 10:04Am
• The Vacation Schedule is used to reduce energy usage during
holidays It does that by lowering the space target between two
date-time settings
• The Vacation Space Target and settings can only be set and
activated using the ICMS website
• The Vacation Schedule Enable must be On to set the Vacation
Schedule and Space Target
The battery is the only backup for
the Date and Time during power
outage The battery can hold the
date and time for up to 100 days