--- Stage Mode is set to Off due to no call for heat/cool
97% Stage Mode is set to Auto The Multi-MOD modulate the stage to the indicated percentage
ON Stage Mode is set to ON The stage ring is at 100% (stage in bypass) See "Mode" on page 39
OFF Stage Mode is set to OFFThe stage is unavailable or does not exist
m95% Stage Mode is set to Manual Manual modulation is set to 95%
C/E The Extension Module stage is NOT communicating back to the Multi-MOD
L/O The stage Lockout input terminals are shorted See "Lockout Inputs Wiring" on page 19

The Multi-MOD Platinum normal display layout uses the second row from the top for operating messages
The following is a list of the most common Message Display Line information:
Ack Received The Internet control has acquired connection to the Heat-Timer communication
server This message is displayed for 2 seconds after one minute of power up
BST: 170˚F Boost is active The new target temperature is 170°F See "Boost and Early
Shutdown" on page 34
DHW Call (180˚F) A DHW Call is active The DHW Set Point is 180˚F See "DHW Set Point" on page 29
Fast Cool Down ESD (Early Shutdown) is active The new target is equal to the Fast Cool Down
setting See "Fast Cool Down" on page 30
Holding Until 150˚F The lead stage is in Last-Stage-Hold This example shows that the lead stage will
turn off when system temperature reaches 150˚F See "Last-Stage-Hold" on page 37
Internet Control The control is an Internet control and the display is in Screen Saver Mode See
"Internet Communication" on page 45
Lag Delay: 123 The lead stage is at 100% and the remaining purge time to start the lag boiler in
seconds is 123 See "Lag Delay" on page 37
Network Panel The control has a communication package installed and the display is in Screen
Saver Mode
Prove Failure After boilers have run for a while, Prove signal was opened All boiler outputs are
de-activated However, the System relay will remain energized See "Prove Wiring"
on page 19
Purge Delay: 23 The current boiler is in purge and the remaining purge time in seconds is 23 See
"Purge Delay" on page 36
Shutdown Active The Shutdown input is shorted/active No stages will be active See "Shutdown
Wiring" on page 18
Shutdown by EMS The EMS set point signal is below 2mA or above 22mA See "EMS Input Mode" on
page 27
System Run-On: 46 The System output is ON for the System Run-On Delay The remaining run-on is 46
seconds before turning off See "System Run-On" on page 34
Waiting for Prove The System output is ON and the prove Input is open No stage output is active See
"Prove Wiring" on page 19