HT# 059299-00 A
• --- Stage Mode is set to Off due to no call for heat/cool
• 97% Stage Mode is set to Auto The Multi-MOD modulate the stage to the indicated percentage
• ON Stage Mode is set to ON The stage ring is at 100% (stage in bypass) See "Mode" on page 39
• OFF Stage Mode is set to OFF The stage is unavailable or does not exist
• m95% Stage Mode is set to Manual Manual modulation is set to 95%
• C/E The Extension Module stage is NOT communicating back to the Multi-MOD
• L/O The stage Lockout input terminals are shorted See "Lockout Inputs Wiring" on page 19
The Multi-MOD Platinum normal display layout uses the second row from the top for operating messages
The following is a list of the most common Message Display Line information:
Ack Received The Internet control has acquired connection to the Heat-Timer communication
server This message is displayed for 2 seconds after one minute of power up
BST: 170˚F Boost is active The new target temperature is 170°F See "Boost and Early
Shutdown" on page 34
DHW Call (180˚F) A DHW Call is active The DHW Set Point is 180˚F See "DHW Set Point" on page 29
Fast Cool Down ESD (Early Shutdown) is active The new target is equal to the Fast Cool Down
setting See "Fast Cool Down" on page 30
Holding Until 150˚F The lead stage is in Last-Stage-Hold This example shows that the lead stage will
turn off when system temperature reaches 150˚F See "Last-Stage-Hold" on page 37
Internet Control The control is an Internet control and the display is in Screen Saver Mode See
"Internet Communication" on page 45
Lag Delay: 123 The lead stage is at 100% and the remaining purge time to start the lag boiler in
seconds is 123 See "Lag Delay" on page 37
Network Panel The control has a communication package installed and the display is in Screen
Saver Mode
Prove Failure After boilers have run for a while, Prove signal was opened All boiler outputs are
de-activated However, the System relay will remain energized See "Prove Wiring"
on page 19
Purge Delay: 23 The current boiler is in purge and the remaining purge time in seconds is 23 See
"Purge Delay" on page 36
Shutdown Active The Shutdown input is shorted/active No stages will be active See "Shutdown
Wiring" on page 18
Shutdown by EMS The EMS set point signal is below 2mA or above 22mA See "EMS Input Mode" on
page 27
System Run-On: 46 The System output is ON for the System Run-On Delay The remaining run-on is 46
seconds before turning off See "System Run-On" on page 34
Waiting for Prove The System output is ON and the prove Input is open No stage output is active See
"Prove Wiring" on page 19