HT# 059299-00 A
• The Setback is used to reduce the system target when less load
is required during the night or on the weekends when a building is
unoccupied, but a minimum level of heat is still required
• To use the Setback, the EMS Input mode must be set to Setback
See "EMS Input Mode" on page 27 Also, the Setback value must
be greater than 0 See "Setback" on page 35
• The Setback can be activated based on the Night Schedule
settings or an external dry-contact Setback input
• When using an external Setback, wire the dry-contact Setback
signal to the EMS terminals (+) and (SIGNAL)
• When the Setback terminals are shorted, the Setback is enabled
and the Multi-MOD Platinum will hold the lower Set Point The
main display will show "
Setback to: 150F" to indicate this
condition
• When the setback signal ends, the Multi-MOD Platinum will revert
to the higher target setting
To avoid damage to the Multi-MOD,
NO VOLTAGE can be applied to the
Multi-MOD Platinum input terminals
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
(DEL)
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
DEL deletes schedule settings
STAGE
(DAY)
HELP NEXT
PRESS TO
SELECT
BACK
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
PRESS
4-20 mA
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
DAY selects next day
SYSTEM B C DA
LINE
NEUTRAL
SYS
B C DA
1 2 3 4
5 6 7 8 9 10 11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
Setback Input
Dry Contact
• The MPC Platinum is a steam cycling outdoor reset control
• The MPC Platinum can be used to activate and deactivate
the Multi-MOD Platinum Shutdown terminals First, the MPC
Platinum Option 2 Relay Mode must be set to Inverse of Output
See MPC Platinum Manual
• Wire the MPC Platinum Option 2 output terminals 15 and 16 to
the Multi-MOD Platinum Shutdown input terminals A3 and A4
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
(DEL)
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
DEL deletes schedule settings
STAGE
(DAY)
HELP NEXT
PRESS TO
SELECT
BACK
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
PRESS
4-20 mA
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
DAY selects next day
SYSTEM B C DA
LINE
NEUTRAL
SYS
B C DA
1 2 3 4
5 6 7 8 9 10 11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
MPC Platinum
Option 1
PREV.
(DEL)
DAY
NEXT
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
SYSTEM AUX
CLOCK
OPTION
1
OPTION
2
OPTION
3
15 16 17 18
OPTION
2
Option 1
Multi-MOD
Platinum
• The HWR Platinum is a hydronic outdoor reset control
• The HWR Platinum is capable of controlling the Multi-MOD
Platinum To set the Multi-MOD Platinum to operate with the
HWR, set the Multi-MOD Platinum Sensor Type to HWR See
"Sensor Type" on page 26
• In the HWR mode, the Multi-MOD Platinum does not require
any sensor The HWR Platinum will have system and outdoor
sensors The HWR Platinum increases or decreases the
Multi-MOD Platinum modulation
• Connect the HWR terminal 11 to the Multi-MOD terminal A6
• Connect the HWR terminal 12 to the Multi-MOD terminal A5
• Connect the HWR terminal 13 to the Multi-MOD terminal A1
MULTI-MOD
Platinum
MADE IN U.S.A.
PREV.
(DEL)
SAFETY
GROUND
MUST BE
CONNECTED
OUT
TEMP
PROVE
/DHW
STAGE
A
STAGE
B
MENU FUNCTIONS
SELECT enters menus or accepts changes
ADJUST selects menu items or changes settings
BACK returns to previous menu
PREV./NEXT steps through stage status
DEL deletes schedule settings
STAGE
(DAY)
HELP NEXT
PRESS TO
SELECT
BACK
ADJUST
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
STAGE
C
DO NOT APPLY ANY VOLTAGE
TO SENSOR TERMINALS
B1
B2
B3
B4
B5
B6
NETWORK
PRESS
4-20 mA
SHUTDOWN
SYSTEM
TEMP
INPUTS
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
<A> B C D
100% 50% --- ---
T
T
OUTPUT RATINGS:
120VAC, 6A RESISTIVE
1A PILOT DUTY
15A TOTAL
FOR ALL CIRCUITS
INPUT RATINGS:
115VAC 60Hz
30VA MAX
USE COPPER WIRE,
CLASS 1 WIRE ONLY
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
LISTED
99RA
STAGE selects stage menus or next stage
DAY selects next day
SYSTEM B C DA
LINE
NEUTRAL
SYS
B C DA
1 2 3 4
5 6 7 8 9 10 11 12
FULL MODULATION
SEQUENCING CONTROL
LOCKOUT
INPUTS
STAGE
D
B7
B8
OPERATING LIMIT
OUTPUTS
SIGNAL
SHIELD
+
EMS
MODULATION OUTPUTS
A B C
D
C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12
S
+
PREV.
(DEL)
PUMP
DAY
HELP NEXT
ROUTE SENSOR AND AUXILIARY WIRES
THROUGH THIS KNOCKOUT ONLY
BURNER
MOTORIZED
VALVE
CLOSE OPEN
OPTION
1
OPTION
2
AUX
CLOCK
PUMP
BURNER
MOTORIZED
VALVE
CLOSE OPEN
OPTION
1
AUX
CLOCK
5 5A 6 7 8
9 11 12 13
Option 1
Multi-MOD
Platinum