EasyManuals Logo

heat-timer Multi-MOD Platinum User Manual

Default Icon
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image


HT# 059299-00 A
The 4-20ma option is used with the 4-20mA temperature sensor
(HT# 904160-00) These sensors can be congured to read temperatures
up to 480°F / 268°C The user must set the 4ma and 20ma temperature
range to match the sensor conguration These sensors' ranges must be
set by Heat-TimerSee "4-20mA Temperature Sensor Wiring" on page 18
Values that are higher than 216mA shall read SHORT Values that are
lower than 24mA shall read OPEN
SENSOR 4mA VALUE
0
F
[
]
SENSOR 20mA VALUE
0
F
[ ]


 
 
 
 /<System Startup>/..../Sensor Type/EMS Input Mode/ EMS 4mA SP/..
Setback allows the Set Point to be adjusted manually
EMS Control allows the set point to be sent remotely using 4-20mA
signal The set point range must be set to match the EMS signal's set
point range using the 4mA and the 20mA temperature settings See
"External Set Point Wiring" on page 22
An active signal must be between 2 and 22mA Any signal out of this
range shuts down the system and displays "Shutdown by EMS"
EMS 4mA SETPOINT
140
F
[
]
EMS 20mA SETPOINT
200
F
[
]
- EMS INPUT MODE -
Setback
EMS Control

 
 
 /<System Startup>/.../Stage Interface/ Stage A Modbus Add/ ...
These options are designed for Modbus operating burners equipped
with the Siemens LMV controller If the burner did not have Modbus
communication, then select Normal
The MODBUS-Monitor Only option receives the alarm lockout status
through the Siemens LMV Interface
The MODBUS-Full Control option sends the modulation percent and
receives the lockout status through the Siemens LMV Interface
Order the LMV Interface for each of the MODBUS burners
(HT# 926621-00) In addition, order the Interface Power Supply
(HT #926622-00) for every 10 burners See LMV-Interface Manual
When any of the Modbus options is selected from the Stage Interface
menu, the Stage Modbus Address will follow
Each Stage address must be unique on the Modbus network
To exit the Stage Modbus Address, enter an address of 0 for the stage
following the last stage
STAGE A MODBUS ADD
1
[
]
STAGE B MODBUS ADD
0
[
]
- STAGE INTERFACE -
Normal
MODBUS-Monitor Only
MODBUS-Full Control

Regardless of the Modbus
options selected, the
Multi-MOD Platinum will also
send a modulation signal to
every active boiler through the
Modulation Output terminals

 
 /<System Startup>/ Sensor Type/.../Output Type A&B
The Multi-MOD Platinum has two Modulating Output Cards Each card
modulates two stages Both stages must use the same modulating
signal See "Modulating Output Card Installation" on page 23
Output Cards can be either 135Ω Cards for 135 ohm modulating motors
or Current/Voltage Cards for current or voltage signal operating motors
-OUTPUT TYPE A&B-
Not Installed
135ohm
0-10v
0-5v
2-10v
1-5v
4-20ma

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the heat-timer Multi-MOD Platinum and is the answer not in the manual?

heat-timer Multi-MOD Platinum Specifications

General IconGeneral
Brandheat-timer
ModelMulti-MOD Platinum
CategoryController
LanguageEnglish