Attaching example of air wind guard
Attach the air flow guide to the air discharge grille with four (4) screws (supplied).
The fixing holes are located at 4 positions on the grille. (Screw tightening torque 2.4 ~ 3.1 N.m)
Do not remove the air discharge grille for air flow guide installation.
C A U T I O N
If the air guide is installed without discharge grille, it may cause injury due to rotating fan.
One windguard cover installation
1 Air discharge grille
2 Wind guard
3 Air discharge grille
4 Outdoor unit
5 M5 fixing screw x4 (Accessories)
Service space
Both sides of the outdoor unit should be open.
No obstacles should be placed in the air discharge side.
1 Min. 200 mm
2 Outdoor unit
3 Wind guard
¿ Snow protection hood
Air discharge hood
Part name Quantity
1 Right side plate 1
2 Left side plate 1
3 Front panel 1
4 Stay 4
5 Fixing screw (Accessories)
6 Hole for safety wire rope to prevent overturning
1
2
3
4
5
1
2
3
1
2
3
4
5
6
2 Unit Installation
35
SMGB0060 rev. 1- 12/2010
2