1-119
TROUBLESHOOTING
Name of Parts Model Electrical Wiring Diagram Wiring No.
Resistance
(Ω)
Fan Motor for Indoor Unit
EHOCM2P4P30
DC Motor - -
for RPK-1.0FSGM,1.5FSGM 30W
2.0FSGM, 2.3FSGM
Fan Motor for Indoor Unit BL "1" - "3" R 127.9
TNO-KPPA R "3" - "5" W 102.7
at 20
o
C
for RPF-1.0FSG, 75W
RPFI-1.0FSG
Fan Motor for Indoor Unit BL "1" - "3" R 127.9
TNO-KPPA R "3" - "5" W 102.7
at 20
o
C
for RPF-1.5FSG, 35W
RPFI-1.5FSG
Fan Motor for Indoor Unit BL "1" - "3" R
112
+10%
TNO-KPPA R "3" - "5" W 77
+10%
for RPC-2.0FSG1 35W
at 20
o
C
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 113
+10%
TNO-KPPA R "3" - "5" W
91
+10%
for RPC-2.5FSG1, 3.0FSG1 50W
at 20
o
C
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 40
+10%
TNO-KPPA R "3" - "5" W 54
+10%
for RPC-4.0FSG1 95W
at 20
o
C
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 25
+10%
TNO-KPPA R "3" - "5" W 40
+10%
for RPC-5.0FSG1 135W
at 20
o
C
(Before Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 81.4
+10%
SF-200-35-4T R "3" - "5" W 99.0
+10%
for RPC-2.0FSG1 35W
at 20
o
C
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R
93.7
+10%
SF-200-50-4W R "3" - "5" W 89.9
+10%
for RPC-2.5FSG1, 3.0FSG1 50W
at 20
o
C
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 20.9
+10%
SF-200-95-4A R "3" - "5" W
31.6
+10%
for RPC-4.0FSG1 95W
at 20
o
C
(After Alteration)
Fan Motor for Indoor Unit BL "1" - "3" R 23.2
+10%
SF-200-135-4C R "3" - "5" W 27.1
+10%
for RPC-5.0FSG1 135W
at 20
o
C
(After Alteration)
1
3
5
1
3
5