1-124
TROUBLESHOOTING
Additional Information for “CHECK LIST ON COMPRESSOR”
Check
Item
Additional Information (Mechanism of Compressor Failure)
1 & 2  The liquid refrigerant return volume to the compressor is controlled by the discharge gas
 temperature Td1 when only No.1 compressor is operating.  If Td1 and Td2 are reversely
 connected, the liquid refrigerant return volume will become small by detecting the temperatures
 even if the actual discharge gas temperature is high.  Therefore, this abnormal overheating
 operation will result in insulation failure of the motor winding.
3, 4 & 5  Overcurrent control (operating frequency control) is performed by detecting current by the
 current sensor.
 In this case, winding insulation failure will occur, since control is not available in spite of actually
 high current.
6 & 7  The current sensor checks phase and adjusts output electrical wave in addition to the above
 mentioned items.  If fault occurs, the output electrical wave becomes unstable giving stress to
 the motor winding, resulting in winding insulation failure.
8 & 9  During a cooling operation, Pd is controlled by fan revolution of outdoor unit, and Td and SH
 are controlled by MV of each indoor units or MVB for FX series.
 During a heating operation, Td and SH are controlled by MV1 and MV2.
 If expansion valves are incorrectly connected, correct control is not available, resulting in
 compressor seizure depending on liquid refrigerant returning conditions or motor winding
 insulation failure depending on overheating conditions.
10  If the refrigeration cycle and electrical system are incorrectly connected, abnormally low
 suction pressure operation is maintained or abnormally high discharge pressure operation is
 maintained, resulting in giving stress to the compressor, since their correct control is not
 available.
11  ditto
12  The compressor may be locked due to the liquid return operation during the cooling operation.
13  In the case that the contacting resistance becomes big, voltage imbalance among each phase
 will cause abnormal overcurrent.
14  In this case, overcurrent will occur, efficiency will decrease or the motor winding will be
  excessively heated.
15  In the case, it will result in motor burning or compressor seizure.