2-9
SERVICING
(2.1 Outdoor Unit)
(8) Disconnect the suction pipe of the compressor.
NOTES:
1. Completely wipe off the oil if the oil is spread to the other parts such as the compressor cover,
wiring, bottom base, etc. If not, this will cause many problems to the unit.
2. If the oil is spilt, charge new oil equivalent to the spilt oil.
3. Check to ensure that the oil is not foul.
If foul, replace it with new one.
TURN OFF all power source switches.
Adjustable Wrench or SpannerTool
Adjustable Wrench or Spanner,
Phillips Screwdriver
Tool
(9) Remove three nuts fixing the compressor and remove the compressor.
NOTE:
When lifting the compressor, hold the discharge pipe vertically and turn it to the right, and pull the
compressor towards the front side by paying attention to the compressor leg not to touch the suction
pipe.
(10) Regarding remounting the compressor work,
perform the above work in the reverse processes.
Suction Pipe
Discharge Pipe
Lift and move towards right.
Pull towards front side.
Oil Heater
Special Nut
Vibration-proof Rubber
Suction Pipe
Pay attention to
this part not to touch
the compressor leg.
Front
Side
Pull out the compressor toward the front side,
and remove the vibration-proof rubbers.